Sustained Pressure | Burst Pressure | ||||||
Nominal pipe size | Pressure Required for Test Psi | Pressure Required for Test Psi | |||||
Schedule 40 | Schedule 80 | Schedule 120 | Schedule 40 | Schedule 80 | Schedule 120 | ||
1/2" | 1250 | 1780 | 2130 | 1910 | 2720 | 3250 | |
3/4" | 1010 | 1440 | 1620 | 1540 | 2200 | 2470 | |
1" | 950 | 1320 | 1510 | 1440 | 2120 | 2300 | |
1 1/2" | 690 | 990 | 1130 | 1060 | 1510 | 1720 | |
2" | 580 | 850 | 990 | 890 | 1290 | 1510 | |
3" | 590 | 790 | 930 | 840 | 1200 | 1420 | |
4" | 470 | 680 | 900 | 710 | 1040 | 1380 | |
6" | 370 | 590 | 780 | 560 | 890 | 1190 | |
8" | 330 | 520 | 760 | 500 | 790 | 1160 | |
10" | 600 | 490 | 770 | 450 | 750 | 1170 | |
12" | 280 | 480 | 710 | 420 | 730 | 1090 |