MAXIMUM SUSTAINED AND BRUST PRESSURE TEST CONDITIONS FOR WATER AT 23o C FOR PVC PIPE

Sustained Pressure   Burst Pressure
Nominal pipe size Pressure Required for Test Psi Pressure Required for Test Psi
Schedule 40 Schedule 80 Schedule 120 Schedule 40 Schedule 80 Schedule 120
1/2" 1250 1780 2130 1910 2720 3250
3/4" 1010 1440 1620 1540 2200 2470
1" 950 1320 1510 1440 2120 2300
1 1/2" 690 990 1130 1060 1510 1720
2" 580 850 990 890 1290 1510
3" 590 790 930 840 1200 1420
4" 470 680 900 710 1040 1380
6" 370 590 780 560 890 1190
8" 330 520 760 500 790 1160
10" 600 490 770 450 750 1170
12" 280 480 710 420 730 1090